Table 1 Relative impact of various factors on phylogenetic and functional microbiome dissimilarity across samples (Adonis and Betadisp, permutation=999)

From: Impact of water heater temperature setting and water use frequency on the building plumbing microbiome

Factor

Phylogenetic

Functional

Samples

 

R 2 Adonis

P Adonis

P Betadisp

R 2 Adonis

P Adonis

P Betadisp

 

Phase

0.246

0.001

0.001

0.087

0.001

0.001

All samples (n=427)

Sample location

0.124

0.001

0.001

0.055

0.001

0.003

All samples (n=427)

t

0.100

0.001

0.001

0.398

0.001

0.001

All samples (n=427)

T

0.172

0.001

0.003

0.194

0.001

0.003

All samples (n=427), influent was set at 20°C.

Water use frequency

0.039

0.001

0.039

0.021

0.005

0.040

Distal tap samples (n=348)

Pipe orientation

0.013

0.006

0.716

0.013

0.008

0.971

Distal tap samples (n=348)

Phase

0.311

0.001

0.001

0.104

0.001

0.001

Distal tap samples (n=348)

Rig

0.025

0.158

0.624

0.019

0.267

0.185

Distal tap at 5 months, 39°C (n = 70)

t (at 39 °C)

0.112

0.001

0.043

0.396

0.001

0.244

Control rig distal tap samples (n=175)

Phase

0.466

0.001

0.001

0.138

0.001

0.001

Control rig distal tap samples (n=175)

t (with elevated T)

0.249

0.001

0.015

0.513

0.001

0.398

Experimental rig distal tap samples (n=173)

Phase

0.256

0.001

0.001

0.084

0.001

0.001

Experimental rig distal tap samples (n=173)

Phase

0.126

0.001

0.098

0.104

0.003

0.069

Recirc. Samples (n=45)

Rig

0.124

0.001

0.003

0.072

0.016

0.962

Recirc. Samples (n=45)

t (at 39 °C)

0.444

0.001

0.730

0.681

0.001

0.519

Control rig recirc samples (n=27)

t (with elevated T)

0.759

0.001

0.687

0.608

0.001

0.807

Experimental rig recirc samples (n=28)

t

0.377

0.001

0.443

0.621

0.001

0.455

Influent (n=24)

Rig

0.041

0.001

0.039

0.012

0.011

0.053

Distal tap samples (n=348)

T (<51 °C or 51 °C)

0.175

0.001

0.001

0.183

0.001

0.001

Experimental rig distal tap samples (n=173)

  1. Both time (t) and water heater temperature setting (T) were treated as non-numeric factors. Statistical significance was set at 0.05: italic font indicates non-statistically significant.