Table 10 Specifications of relevant sensors from the FLEXLAB and FRP experimental facilities.

From: Building fault detection data to aid diagnostic algorithm creation and performance testing

Facility

Sensor

Measurement

Accuracy

FLEXLAB

BAPI BA/10K-2(XP)-D-12′′-BB thermistor

Temperature

±0.1 °C

FRP

Campbell Sci HC2S3-L

Temperature, relative humidity (RH)

±0.1 °C and ±0.8% RH @ 23 °C

 

Continental Controls WNB-3D-240P

Power

±0.5% of reading

 

Omega PX409-750-A5V pressure transducer

Pressure

±0.08% best straight line maximum

 

Air Monitor fan evaluator paired with Veltron DPT2500-Plus transmitter

Air flow

DPT2500, 0.25% of natural span, including hysteresis, deadband, nonlinearity, and nonrepeatability

Fan evaluator ±2%