Table 7 Methods of fault imposition for each of the multi-zone VAV AHU #2-2 faults.

From: Building fault detection data to aid diagnostic algorithm creation and performance testing

Input Scenarios

Method of fault imposition

Fault type

Fault intensity

OA Damper

Stuck

Fully closed

Automated override of control signal values to indicate that OA damper is stuck.

40% open

45% open

55% open

Valve of Heating Coil

Leaking

Stage 1: 1.5 SLM

Manually open heating coil bypass valve

Stage 2: 3.7 SLM

Stage 3: 7.5 SLM

Valve of Cooling Coil

Stuck

Fully closed

Automated override of control signal values to indicate that cooing coil valve is stuck.

Fully open

Partially open 15%

Partially open 65%

Unfaulted