Table 3 Methods of fault imposition.
Fault types | Fault scenarios | Methods of fault imposition |
---|---|---|
Open LT display case door | 5%, 10%, 15% of the time | Program an automatic door open device to control the door open time |
Ice accumulation on LT evaporator coil | Mild, moderate, severe | Manually set the daily defrost times to build up the ice on the evaporator coil |
LT evaporator expansion valve failure | Partially closed, Fully closed | Manually adjust the evaporator expansion valve opening position |
MT evaporator fan motor failure | 25%, 50%, 75% | Sequentially turn off three of four MT evaporator fans |
Condenser air path blockage | 25%, 50%, 75% | Block the condenser coil inlet air path |
MT evaporator air path blockage | 25%, 50%, 75% | Block the MT evaporator coil return air path |