Table 8 Measurement variables and instrumentation used to collect data.

From: Datasets of a Multizone Office Building under Different HVAC System Operation Scenarios

Measured data

Instrument

Range

Accuracy

Weather data

Outdoor air temperature

Campbell Sci HC2S3-L

~−50–100 °C

±0.1 °C

Outdoor air humidity

~0%–100%

±0.8% at 23 °C

Barometric pressure

CS106 - Vaisala

500–1,100 hPa

±0.3 hPa at 20 °C

±0.6 hPa (0 to 40 °C)

±1.0 hPa (−20 to +45 °C)

±1.5 hPa (−40 to +60 °C)

Direct solar radiation

Eppley sNIP (Normal Incidence Pyrheliometer)

Spectral range: ~250–3,500 nm, Output: 0–10 mV

±1% of reading (hourly)

Diffuse solar radiation

Eppley Model 8–48 (The Diffuse Pyranometer)

Spectral range: ~295–2,800 nm, Output: 0–10 mV

±2% of reading (hourly)

Global solar radiation

Eppley SPP (Standard Precision Pyranometer)

Spectral range: ~295–2,800 nm, Output: ~0–10 mV

±2% of reading (hourly)

Wind speed

Young Wind Monitor Model 05103

~0–100 m/s

±0.3 m/s or 1% of reading

Wind direction

~0°–360°

±3°

Building data

Indoor air temperature

Campbell Sci HC2S3-L

~−50–100 °C

±0.1 °C

Supply air temperature

Return air temperature

Indoor air relative humidity

~0%–100%

±0.8% at 23 °C

Supply air relative humidity

Return air relative humidity

Compressor electric energy consumption

Continental Controls WNB-3D-240P

~0–72,000 W

±0.5% of reading

Condenser electric energy consumption

Re-heating coil electric energy consumption

Fan electric energy consumption

Airflow rate (RTU fan)

Air monitor fan evaluators paired to DPT2500 Plus transmitters

~0–20.32 m/s

Fan evaluator: ±2%

DPT2500 Plus transmitters: ±0.25% of natural span

Airflow rate (VAV boxes)

EF-x2000-T (EBTRON)

~0–15.24 m/s

±3% of reading