Table 7 Losses and minimum load voltage before and after the capacitor placement in the scenario of connected to the network with cosφ = 1.
SHO | GA20 | |||||
---|---|---|---|---|---|---|
Level 1 | Level 2 | Level 3 | Level 1 | Level 2 | Level 3 | |
Before cap placement | ||||||
Loss (kW) | 46.064 | 169.018 | 315.979 | 46.064 | 169.018 | 315.979 |
Minimum voltage (p.u) | 0.9928 | 0.9779 | 0.9499 | 0.9928 | 0.9779 | 0.9499 |
After cap placement | ||||||
Loss (kW) | 28.21 | 65.40 | 123.24 | 28.632 | 68.311 | 123.953 |
Minimum voltage (p.u) | 0.9987 | 0.9916 | 0.9739 | 0.9989 | 0.9894 | 0.9728 |