Table 3 Switchgear control based on control authority6.
From: A novel hybrid methodology to secure GOOSE messages against cyberattacks in smart grids
Control parameters | Control authority at each level | ||||||
---|---|---|---|---|---|---|---|
Switch | Bay control | Manual control | Originator category (OrCat) | ||||
XCBR.Loc XSWI.Loc | LLNO.MltLev | CSWI.Loc | CSWI.LocSta | Processa | Bayb | Stationc | Remotec |
TRUE | FALSE | Not applicable | Not applicable | Always allowed | Not allowed | Not allowed | Not allowed |
FALSE | FALSE | TRUE | Not applicable | Always allowed | Always allowed | Not allowed | Not allowed |
FALSE | FALSE | FALSE | TRUE | Always allowed | Not allowed | Always allowed | Not allowed |
FALSE | FALSE | FALSE | FALSE | Always allowed | Not allowed | Not allowed | Always allowed |
TRUE | TRUE | Not applicable | Not applicable | Always allowed | Not allowed | Not allowed | Not allowed |
FALSE | TRUE | TRUE | Not applicable | Always allowed | Always allowed | Not allowed | Not allowed |
FALSE | TRUE | FALSE | TRUE | Always allowed | Always allowed | Always allowed | Not allowed |
FALSE | TRUE | FALSE | FALSE | Always allowed | Always allowed | Always allowed | Always allowed |