Table 3 Active and reactive power flow and losses and % PF for every bus.

From: Study of power quality issues without and with Microgrid in Egypt

ID

Type

KW Flow

KVar Flow

% PF

KW Losses

KVar Losses

Normal load cable

Cable

397.9

211

88.34

6.45

4.82

Normal load cable 2

Cable

397.9

211

88.34

1.29

1.1

Transformer

Transf

814.6

500.3

85.22

12.55

43.94

Water pump cable

Cable

389.2

233.5

85.75

6.89

5.36

Water pump cable2

Cable

396

238.9

85.63

6.89

5.36