Table 9 Operating time for single line-to-ground fault with Rf = 50 Ω at tf = 0.06 s
From: Adaptive overcurrent protection considering fault current limiters effect
Distance | Operating time (OPT) Single line-to-ground fault with Rf = 50 Ω at tf = 0.06 s ZL = j120.26 + j26.99 Ω | |||||||
|---|---|---|---|---|---|---|---|---|
Conventional OCR | Adaptive OCR | |||||||
Without FCL Without DGSM | Without FCL With DGSM | With FCL Without DGSM | With FCL With DGSM | Without FCL Without DGSM | Without FCL With DGSM | With FCL Without DGSM | With FCL With DGSM | |
1000 m | 2.528 | 2.516 | 2.528 | 2.516 | 2.3551 | 2.3551 | 2.3551 | 2.3551 |
2000 m | 2.578 | 2.576 | 2.578 | 2.576 | 2.4062 | 2.4062 | 2.4062 | 2.4062 |
3000 m | 2.648 | 2.638 | 2.648 | 2.638 | 2.4515 | 2.4515 | 2.4515 | 2.4515 |
4000 m | 2.710 | 2.692 | 2.710 | 2.692 | 2.4993 | 2.4895 | 2.4993 | 2.4895 |
5000 m | 2.767 | 2.751 | 2.767 | 2.751 | 2.5396 | 2.5396 | 2.5396 | 2.5396 |