Table 1 Parameter values of DFIG and SVC.

From: Voltage stability assessment and improvement of Ethiopian 230 kv wind-integrated grid using SVC and continuation power flow in PSAT

Wind Energy Resource (DFIG)

Voltage and power rating

[230KV, 120 MW]

Frequency

50 Hz

Stator resistance (Rs) and reactance (Xs)

(0.01, 0.10)p.u

Rotor resistance (Rr) and reactance (Xr)

(0.01, 0.08)p.u

Magnetization reactance (Xm)

3.00p.u

Inertia constants (Hm)

8kws/kVA

Pitch contrl gain (Kp)

10p.u

Time constant

3(s)

Power control time constant (Te)

0.01(s)

No. of poles and gear box ratio

[4,1/89]

Blade length

75.0(m)

No. of blades

3

Pmax and Pmin

[1.0, 0.0]p.u

Qmax and Qmin

[0.7,−0.7]p.u

No. of wind generator

01

Static Var Compensator (SVC)

Voltage and power rating

[400kv, 120 MW]

Frequency

50HZ

Regular time constant Tr

10(s)

Regular gain Kr

100 p.u

Reference voltage

1.0p.u