Table 2 Numerical results of scenario#1 optimization for modified 33-bus distribution network.
Method/Item | Base Net | IDO | DO | GWO | PSO | AOA |
---|---|---|---|---|---|---|
Opened switches | 33, 34, 35, 36, 37 | 10, 20, 28, 30, 35 | 7, 12, 21, 28, 32 | 7, 9, 12, 27, 32 | 7, 10, 12, 28, 32 | 7, 12, 21, 28, 36 |
PV location (@bus)/Size (kW)/p.f | – | @7/894/0.86 | @29/938/0.87 | @25/965/0.83 | @8/947/0.84 | @29/971/0.85 |
Power loss (kW) | 207.44 | 112.79 | 120.22 | 115.63 | 114.11 | 117.06 |
Voltage sag (p.u) | 0.96 | 0.42 | 0.50 | 0.47 | 0.46 | 0.51 |
THD (%) | 0.1835 | 0.1725 | 0.1793 | 0.1791 | 0.1731 | 0.1734 |
Voltage unbalance (%) | 4.92 | 2.07 | 2.26 | 2.28 | 2.14 | 2.17 |
Energy not-supplied (MWh) | 6.44 | 5.13 | 5.29 | 5.26 | 5.24 | 5.33 |
SAIFI (failure/customer/yr) | 1.36 | 1.18 | 1.22 | 1.23 | 1.21 | 1.31 |
SAIDI (hour/customer/yr) | 1.21 | 1.03 | 1.14 | 1.12 | 1.06 | 1.09 |
MAIFI (mom/customer/yr) | 4.64 | 2.38 | 2.47 | 2.44 | 2.45 | 2.56 |
Objective function | 1 | 0.6715 | 0.7163 | 0.7074 | 0.6894 | 0.7157 |