Table 3 Summary of comparative performance analysis.

From: Dual-tree wavelet transform based advanced adaptive control for seamless transition in PV-battery hybrid microgrid system

Testing platform

Mode/condition

Current THD (%)

PQ improvement (%)

Overall improvement (%)

Avg. settling time (Sec)

Load satisfaction

Simulation

GF @ Inv-1 Failure

Grid: 0.136

Grid: 99.52

Grid: 99.54

0.03–0.06

High

GF @ Variable Generation

Grid: 0.05

Grid: 99.83

Grid: 99.82

0.02–0.07

High

GF & GFm Combined

Grid: 0.113

Grid: 99.6

Grid: 99.59

0.02–0.05

High

Real-time

No Controller

Grid: 35.2

NA

NA

NA

Poor

DWT-AC

Grid: 5.3

84.94

84.93

0.7

Moderate

DTWT-AAC

Grid: 1.9

94.6

94.6

0.3

High