Table 10 Effect of fault types, fault location, fault inception time and fault resistance for WSCC 9 bus system.

From: Directional protection scheme using impedance approach for transmission lines

The considered conditions

Results

Fault types

Fault location

Resistance (Ω)

Inception

Instant (sec)

Z matrix value

Direction result

AG

F

1

0.156

-2.4

F

AG

R

20

0.156

2.8

R

CG

F

100

0.183

-2.9

F

BG

R

60

0.166

3.4

R

ACG

F

25

0.174

-3.7

F

CG

R

1

0.131

3.5

R

AB

F

1

0.152

-1.9

F

ABG

R

100

0.162

2.8

R

AC

F

25

0.184

-2.8

F

ACG

R

15

0.198

2.7

R

ABC

F

0.5

0.169

-3.5

F

BCG

R

35

0.182

3.8

R

BG

F

50

0.192

-3.5

F

AB

R

0.1

0.171

4.1

R

ABG

F

0.5

0.191

-4.2

F

BC

R

1

0.175

2.7

R

BCG

F

30

0.168

-2.4

F

AC

R

50

0.177

3.8

R

BC

F

100

0.165

-3.4

F

ABCG

R

100

0.183

2.8

R

ABCG

F

1

0.158

-3.7

F

ABC

R

0.5

0.171

4.2

R