Table 11 Influence of different fault parameters (types, fault location, fault time, fault resistance, load angle) for transmission system model equipped with shunt reactors.

From: Directional protection scheme using impedance approach for transmission lines

The considered conditions

Results

Fault types

Fault position

Resistance (Ω)

Inception

Instant (sec)

Load angle of sources (degree)

Z matrix value

Direction result

AG

Forward

10

0.18

5

-3.2

Forward

AG

Reverse

8

0.19

10

4.5

Reverse

CG

Forward

5

0.15

8

-6.2

Forward

CG

Reverse

50

0.17

9

4.9

Reverse

ACG

Forward

11

0.14

11

-3.9

Forward

ACG

Reverse

15

0.16

12

5.2

Reverse

AB

Forward

10

0.18

5

-6.8

Forward

AB

Reverse

25

0.16

4

4.2

Reverse

BC

Forward

30

0.14

6

-3.8

Forward

BC

Reverse

5

0.17

3

5.7

Reverse

ABCG

Forward

1

0.15

10

-6.4

Forward

ABCG

Reverse

0

0.19

12

4.9

Reverse

ABC

Forward

9

0.16

5

-7.0

Forward

ABC

Reverse

15

0.14

9

3.8

Reverse

BC

Forward

25

0.15

8

-5.7

Forward

BC

Reverse

2

0.18

6

4.6

Reverse

AC

Forward

10

0.17

7

-5.8

Forward

AC

Reverse

40

0.14

4

6.4

Reverse

BCG

Forward

5

0.16

6

-5.7

Forward

BCG

Reverse

30

0.18

9

5.2

Reverse

ACG

Forward

50

0.15

8

-4.6

Forward

ACG

Reverse

1

0.17

10

5.0

Reverse