Table 3 Influence of different fault parameters (types, fault location, fault time, fault resistance, load angle) for a single circuit line (Scenario 1).

From: Directional protection scheme using impedance approach for transmission lines

The considered conditions

Results

Fault types

Fault position

Resistance (Ω)

Inception

Instant (sec)

Load angle of sources (degree)

Z matrix value

Direction result

ABCG

Forward

3

0.18

11

-4.3

Forward

ABCG

Reverse

2

0.17

5

6.6

Reverse

ABC

Forward

35

0.17

9

-3.9

Forward

ABC

Reverse

40

0.16

8

5.5

Reverse

BC

Forward

16

0.15

12

-4.7

Forward

BC

Reverse

16

0.15

9

5.4

Reverse

AC

Forward

20

0.13

12

-4.2

Forward

AC

Reverse

25

0.16

16

6.8

Reverse

BCG

Forward

20

0.14

8

-3.9

Forward

BCG

Reverse

15

0.17

10

4.5

Reverse

ACG

Forward

35

0.17

5

-4.9

Forward

ACG

Reverse

75

0.15

8

4.6

Reverse

AB

Forward

1

0.18

15

-4.9

Forward

AB

Reverse

2

0.16

5

5.6

Reverse

CG

Forward

3

0.17

12

-4.8

Forward

CG

Reverse

5

0.17

16

4.0

Reverse

ABG

Forward

5

0.18

4

-3.6

Forward

ABG

Reverse

5

0.15

14

6.9

Reverse

AG

Forward

20

0.15

6

-4.8

Forward

AG

Reverse

75

0.17

4

3.9

Reverse

BG

Forward

5

0.14

12

-5.2

Forward

BG

Reverse

5

0.18

5

4.1

Reverse