Table 7 Changing the source impedance PPS behavior (scenario 16).

From: Directional protection scheme using impedance approach for transmission lines

The conditions studied

Results

Impedance

Z1SA (Ω)

Impedance

Z1SB (Ω)

Fault types

Fault position

Resistance (Ω)

Z matrix value

Direction result

0.72 + J8.2

1.4 + J1.6

AG

F

20

-1.9

F

0.72 + J8.2

1.1 + J1.3

AG

R

30

3.5

R

0.09 + J2.5

1.3 + J1.5

BG

F

15

-1.6

F

0.09 + J2.5

1.4 + J.6

BG

R

5

2.5

R

0.59 + J6.7

1.1 + J1.3

CG

F

15

-4.2

F

0.59 + J6.7

1.3 + J1.5

CG

R

20

3.6

R

0.72 + J8.2

1.4 + J1.6

ABG

F

35

-3.8

F

0.72 + J8.2

1.1 + J1.3

ABG

R

15

3.9

R

0.09 + J2.5

1.3 + J1.5

ACG

F

5

-2.6

F

0.09 + J2.5

1.4 + J1.6

ACG

R

10

5.9

R

0.59 + J6.7

1.1 + J1.3

BCG

F

15

-1.8

F

0.59 + J6.7

1.3 + J1.5

BCG

R

30

4.4

R

0.72 + J8.2

1.4 + J1.6

AB

F

20

-3.3

F

0.72 + J8.2

1.1 + J1.3

AB

R

5

3.1

R

0.09 + J2.5

1.3 + J1.5

BC

F

24

-3.2

F

0.09 + J2.5

1.4 + J1.6

BC

R

38

2.8

R

0.59 + J6.7

1.1 + J1.3

AC

F

5

-2.5

F

0.59 + J6.7

1.3 + J1.5

AC

R

15

5.6

R

0.09 + J2.5

1.4 + J1.6

ABCG

F

26

-3.7

F

0.72 + J8.2

1.1 + J1.3

ABCG

R

1

3.3

R

0.59 + J6.7

1.3 + J1.5

ABC

F

18

-2.9

F

0.09 + J2.5

1.4 + J1.6

ABC

R

10

4.7

R