Table 9 PPS behavior under dissimilar transmission line length (scenario 18).

From: Directional protection scheme using impedance approach for transmission lines

The considered conditions

Results

Line length (Km)

Fault types

Fault position

Resistance (Ω)

Z matrix value

Direction result

70

AG

F

1

-2.4

F

140

AG

R

40

2.5

R

140

ABG

F

25

-3.8

F

200

ABG

R

20

3.2

R

200

AB

F

100

-2.8

F

80

ABCG

R

35

2.9

R

100

ABCG

F

25

-4.1

F

120

CG

F

0.5

-3.7

F

180

CG

R

1

3.8

R

160

BCG

F

50

-4.6

F

70

BCG

R

100

4.8

R

80

AC

F

0.5

-3.4

F

200

AC

R

0.5

3.5

R

80

ABCG

F

13

-4.2

F