Table 2 Protection, simulation, and optimization parameters used in the test systems.

From: Performance evaluation of advanced metaheuristic algorithms for directional overcurrent relay coordination in distribution networks

Category

Parameter

Value

Metaheuristic

Algorithm

Parameters

Total number of relays

3-bus: 6; 8-bus: 14; 15-bus: 42

Fault scenarios (line regions)

3-bus: 3 (5–6, 2–1, 4–3)

 

8-bus: 7 (13–6,..., 4–11)

 

15-bus: 21 (1–2,..., 41–42)

Simulation horizon

0.02 s

Fault application time

0.01 s

TMS bounds

[0.05, 1.5]

PS/\(I_{\text {pickup}}\) (optimized)

Optimized, \(\Delta I_p\) [A]

CTI

0.01 s

Relay curve type

IEC/IEEE Standard Inverse

Curve constants

\(A = 0.14\), \(B = 0.02\)

Relay time limits

0.01–3 s

Population size

20 (applies to all algorithms)

Max. iterations

100 (applies to all algorithms)

Algorithms and Parameters

AVOA parameters

\(p = 0.8\), \(P_{1} = 0.6\), \(P_{2} = 0.4\), \(p_{3} = 0.4\), Levy \(\beta = 1.5\), step size \(= 0.01\)

ARO parameters

Shape factor \(A_{0} = 4\) in

\(A = 4(1 - t/N_{\max })\log (1/r)\)

NOA parameters

\(\sigma _{1} = 0.5\), \(\gamma = 0.5\), \(\lambda = 0.2\), \(P_{\textrm{rp}} = 0.6\), \(p_{a1}(i), p_{a2}(i) \in [0,1]\)

TSO parameters

Galaxy-phase samples \(SN_{1} = 5\);

planet/neighbour samples \(SN_{2} = 3\)

ZOA parameters

Step-size coefficient \(R = 0.01\)