TableĀ 3 Power quality estimation during non-linear load applications.

From: Advanced control scheme for harmonic mitigation and performance improvement in DC-AC microgrid with parallel voltage source inverter

Component

Metric

Droop (without SAPF)

SRF based FCS-MPC (with SAPF)27

FS-MPC (with SAPF)

Improvement over Droop%

Improvement over SRF basd FCS-MPC%

Non-linear Load Current

THD% Load

38.89%

38.89%

38.89%

–

–

Grid Current

THD% Grid

38.89%

6.5%

2.1%

94.60%

67.69%

Mean THD

μTHD

\(\begin{gathered} \mu = \frac{38.89 + 38.89}{2} \hfill \\ = 38.89\% \hfill \\ \end{gathered}\)

\(\mu = \frac{38.89 + 6.5}{2} = 22.70\%\)

\(\mu = \frac{38.89 + 2.1}{2} = 20.50\%\)

–

–

Standard Deviation

SDTHD

\(SD_{THD} = 0\)

\(\begin{gathered} SD_{THD} = \hfill \\ \sqrt {\frac{{\left( {38.89 - 22.70} \right)^{2} + \left( {6.5 - 22.70} \right)^{2} }}{2}} \hfill \\ = 16.91\% \hfill \\ \end{gathered}\)

\(\begin{gathered} SD_{THD} = \hfill \\ \sqrt {\frac{{\left( {38.89 - 20.50} \right)^{2} + \left( {2.1 - 20.50} \right)^{2} }}{2}} \hfill \\ = 25.88\% \hfill \\ \end{gathered}\)

–

–