Table 5 Simulation result of 69 bus test system considering various load models (Case 3).

From: Techno-economic analysis of distribution system at various load models using MEWOA algorithm

Algorithm/Cases

Item/Load

DG size (kVA)

SC size (kVar)

PTL (kW)

QTL (kW)

Vmin (p.u)

VSImin (p.u)

DA

COM

2373.40

987.19

5.83

7.61

0.9944

0.9594

CZ

2161.26

1134.85

5.85

7.52

0.9940

0.9592

RES

2458.78

976.39

5.86

9.41

0.9944

0.9594

IND

2752.59

417.43

5.88

7.16

0.9944

0.9594

CI

2212.28

993.46

6.32

7.58

0.9921

0.9590

CP

2731.12

237.24

6.81

7.82

0.9943

0.9587

WOA

COM

2345.29

737.20

4.68

6.74

0.9943

0.9545

CZ

2403.19

532.04

4.80

6.81

0.9943

0.9544

RES

2363.44

1146.43

4.92

6.78

0.9944

0.9545

IND

2456.07

452.82

5.28

6.95

0.9944

0.9546

CI

2190.50

1221.27

5.44

7.24

0.9943

0.9590

CP

2716.50

733.80

5.57

7.24

0.9943

0.9588

GOA

COM

2621.22

145.67

3.81

6.43

0.9944

0.9593

CZ

2288.85

966.59

3.83

6.45

0.9943

0.9592

RES

2387.84

1260.73

3.86

6.46

0.9944

0.9593

IND

2519.61

1043.55

3.89

6.47

0.9944

0.9594

CI

2737.15

316.09

4.03

6.59

0.9943

0.9590

CP

2794.28

646.99

4.27

6.75

0.9944

0.9588

MEWOA

COM

2548.03

321.30

3.83

6.43

0.9944

0.9593

CZ

2400.98

621.64

3.85

6.45

0.9943

0.9592

RES

2389.74

1016.44

3.87

6.47

0.9944

0.9593

IND

2519.21

1178.06

3.89

6.47

0.9944

0.9594

CI

2747.78

250.28

4.08

6.62

0.9943

0.9590

CP

2551.42

1481.61

4.29

6.76

0.9944

0.9588