Table 4 Optimization results for the IEEE 69-bus feeder.
 | Capacitor I | Capacitor II | Total voltage deviation (pu) | Loss (kw) | Cost ($) | Loss reduction percentage | ||
---|---|---|---|---|---|---|---|---|
Bus number | Capacity (KVar) | Bus number | Capacity (KVar) | |||||
Base | - | - | - | - | 13.18 | 1226.7 | 1932 | 0 |
NSGAII | 19 | 1350 | 59 | 470 | 10.45 | 932 | 1673 | 24.02 |
MODE | 17 | 1365 | 57 | 540 | 10.83 | 918 | 1592 | 25.17 |
MOGWO | 14 | 1270 | 54 | 635 | 9.79 | 935 | 1714 | 23.78 |
MOPSO | 12 | 1385 | 60 | 430 | 9.32 | 907 | 1507 | 26.06 |