Table 4 Pre and Post Retrofit Blower door test results.
From: Dataset on occupant behavior, indoor environment, and energy use before and after dormitory retrofit
Dorm ID | Volume (ft3) | Exterior Enclosure Area (ft2) | Pre-Retrofit | Post-Retrofit (HRV Blocked) | ||||||
|---|---|---|---|---|---|---|---|---|---|---|
CFM50 | ACH50 | ACH (CC Conv) | CFM50/ft2 | CFM50 | ACH50 | ACH (CC Conv) | CFM50/ft2 | |||
1 | 6200 | 1671 | 439 | 4.25 | 0.43 | 0.26 | 191 | 1.85 | 0.19 | 0.11 |
2 | 6200 | 1175 | 205 | 1.98 | 0.20 | 0.17 | 144 | 1.39 | 0.14 | 0.12 |
3 | 6200 | 1175 | 223 | 2.16 | 0.22 | 0.19 | 139 | 1.35 | 0.14 | 0.12 |
4 | 6200 | 1175 | 307 | 2.97 | 0.30 | 0.26 | 139 | 1.35 | 0.14 | 0.12 |
5 | 6200 | 1175 | 338 | 3.27 | 0.33 | 0.29 | 162 | 1.57 | 0.16 | 0.14 |
6 | 6200 | 1175 | 276 | 2.67 | 0.27 | 0.23 | 123 | 1.19 | 0.12 | 0.1 |
7 | 6200 | 1175 | 402 | 3.89 | 0.39 | 0.34 | 121 | 1.17 | 0.12 | 0.1 |
8 | 6200 | 1671 | 503 | 4.87 | 0.49 | 0.3 | 119 | 1.15 | 0.12 | 0.07 |
Avg. | 0.33 | 0.14 | ||||||||
Total | 49600 | 10392 | ||||||||