Table 4 Pre and Post Retrofit Blower door test results.

From: Dataset on occupant behavior, indoor environment, and energy use before and after dormitory retrofit

Dorm ID

Volume (ft3)

Exterior Enclosure Area (ft2)

Pre-Retrofit

Post-Retrofit (HRV Blocked)

CFM50

ACH50

ACH (CC Conv)

CFM50/ft2

CFM50

ACH50

ACH (CC Conv)

CFM50/ft2

1

6200

1671

439

4.25

0.43

0.26

191

1.85

0.19

0.11

2

6200

1175

205

1.98

0.20

0.17

144

1.39

0.14

0.12

3

6200

1175

223

2.16

0.22

0.19

139

1.35

0.14

0.12

4

6200

1175

307

2.97

0.30

0.26

139

1.35

0.14

0.12

5

6200

1175

338

3.27

0.33

0.29

162

1.57

0.16

0.14

6

6200

1175

276

2.67

0.27

0.23

123

1.19

0.12

0.1

7

6200

1175

402

3.89

0.39

0.34

121

1.17

0.12

0.1

8

6200

1671

503

4.87

0.49

0.3

119

1.15

0.12

0.07

Avg.

    

0.33

   

0.14

 

Total

49600

10392