Table 2 The measured PQ data (Decision matrix).

From: Comprehensive power quality performance assessment for electrical system of a nuclear research reactor

Alternatives

F_dev

V_Un

I_Un

Pst

Plt

VTHD

ITHD

PF

Sample 1

0.14508

0.0935

3.2588

0.105193333

0.085046667

0.844866667

5.8457

0.9684

Sample 2

0.25958

0.065

4.2029

0.105323333

0.109903333

0.965

8.030833333

0.9747

Sample 3

0.15946

0.0323

3.1262

0.126253333

0.158126667

0.967466667

7.130566667

0.964

Sample 4

0.18056

0.0708

2.8682

0.106096667

0.142603333

1.2088

6.127033333

0.9661

Sample 5

0.31088

0.0739

3.6941

0.097556667

0.10393

0.908266667

6.840866667

0.9648

Sample 6

0.26864

0.0323

2.0803

0.13881

0.20178

0.9539

5.280833333

0.9523