Table 2 Audible and visible corona voltage of deep under-ribs and alternating shed insulator under clean and polluted conditions.
Test name | Type of insulator | Audible corona corresponding leakage current | Visible corona corresponding leakage current | ||
|---|---|---|---|---|---|
Clean insulator | Polluted insulator | Clean insulator | Polluted insulator | ||
Power frequency flashover test | Deep under-ribs insulator | 30.0Â kV 0.174Â mA | 19.54Â kV 0.761Â mA | 75Â kV 0.296Â mA | 67.59Â kV 2.429Â mA |
Alternating shed insulator | 22.49Â kV 0.079Â mA | 20.3Â kV 0.479Â mA | 72Â kV 0.304Â mA | 70.63Â kV 1.783Â mA | |