Table 3 Power frequency flashover test results of deep under-ribs and alternating shed insulator under clean and polluted conditions.
Test name | Type of insulator | Flashover voltage and corresponding leakage current | |
|---|---|---|---|
Clean insulator | Polluted insulator | ||
Power frequency flashover test | Deep under-ribs insulator | 106.08Â kV 2.920Â mA | 101.02Â kV 3.736Â mA |
Alternating shed insulator | 133Â kV 2.606Â mA | 128.7Â kV 3.557Â mA | |