Table 3 Best parameters solution of OPF problem extracted from SAR method based on OPFFF2 for IEEE 14-bus system.
From: Optimum solution of power flow problem based on search and rescue algorithm
Parameters | Units | Best value |
|---|---|---|
P1 | MW | 2.93397270953455 |
P2 | MW | 115.306330604569 |
P3 | MW | 4.48038946406919 |
P6 | MW | 40.3951253628995 |
P8 | MW | 99.8941703336029 |
V1 | \(\:p.u\) | 0.999670186231509 |
V2 | \(\:p.u\) | 1.00038375267525 |
V3 | \(\:p.u\) | 0.999856284023542 |
V6 | \(\:p.u\) | 1.00874226264043 |
V8 | \(\:p.u\) | 1.02654389444729 |
T4-7 | -- | 1.01393163540060 |
T4-9 | -- | 1.07013425188454 |
T5-6 | -- | 1.06253669273422 |
QC14 | MVAR | 4.98510379628612 |
Total cost of fuel in ($/h) | 11596.1581994691 | |
Power losses in MW | 4.00743987612710 | |
Fitness function (Voltage deviation) | 0.0357680148269292 | |