Table 3 Summary of cases 1, 2 and 3 single-objective optimization considering HC, network losses and VDev without and with DR consideration.
Cases | C-1 | C-2 | C-3 | |||
|---|---|---|---|---|---|---|
Objective—maximize HC | Objective—minimize losses | Objective—minimize Voltage deviation | ||||
Without DR | With DR | Without DR | With DR | Without DR | With DR | |
CapPPV1 [kW] | 348.49 | 2771.48 | 804.68 | 934.67 | 1244.89 | 1471.44 |
CapPPV2 [kW] | 2448.57 | 630.94 | 1038.43 | 1200.01 | 1510.00 | 1851.27 |
HC [kW] | 2797.07 | 3402.43 | 1843.11 | 2134.69 | 2754.90 | 3322.71 |
Loss [kWh] | 1653.19 | 1913.215 | 1418.50 | 1197.10 | 1490.02 | 1316.40 |
VDev [p.u.] | 0.705 | 0.705 | 0.719 | 0.558 | 0.676219882 | 0.498108 |