Table 4 Air temperature, relative humidity, and bioaerosols (bacterial and fungal) concentration in different wards of selected hospitals during seasons.

From: Seasonal evaluation of culturable bioaerosols and airborne particulate matter in Iranian hospital wards using a Monte Carlo health risk model

Hospital

Ward

Season

SP

SU

AU

WI

TEMP. (°C)

HU. (%)

Bacterial Con. (± SD) (cfu/m3)

Fungal Con. (± SD) (cfu/m3)

TEMP. (°C)

HU. (%)

Bacterial Con. (± SD) (cfu/m3)

Fungal Con. (± SD) (cfu/m3)

TEMP. (°C)

HU. (%)

Bacterial Con. (± SD) (cfu/m3)

Fungal Con. (± SD) (cfu/m3)

TEMP. (°C)

HU. (%)

Bacterial Con. (± SD) (cfu/m3)

Fungal Con. (± SD) (cfu/m3)

A

OR

24.3

53.0

6 (± 15)

2 (± 28)

24.7

51.3

124 (± 85)

94 (± 83)

23.8

54.8

196 (± 142)

108 (± 8)

23.5

50.0

87 (± 3)

216 (± 215)

EM

22.8

57.3

5 (± 8)

1 (± 18)

24.5

64.9

534 (± 50)

776 (± 1012)

24.2

61.6

428 (± 155)

118 (± 43)

24.9

49.9

140 (± 73)

465 (± 412)

INT

24.0

55.4

136 (± 3)

32 (± 15)

23.8

65.9

300 (± 195)

122 (± 172)

23.2

58.1

124 (± 50)

223 (± 60)

23.5

37.9

64 (± 35)

62 (± 33)

Mean

23.7

55.2

49 (± 9)

12 (± 20)

24.3

60.7

319 (± 110)

331 (± 422)

23.7

58.2

249 (± 116)

150 (± 37)

24.0

45.9

97 (± 37)

248 (± 220)

B

OR

25.0

52.2

228 (± 28)

30 (± 3)

24.3

52.0

216 (± 115)

179 (± 117)

23.2

57.3

131 (± 10)

42 (± 20)

22.6

56.6

83 (± 8)

71 (± 20)

EM

24.6

51.6

152 (± 15)

48 (± 18)

26.4

43.4

767 (± 45)

120 (± 80)

27.1

41.2

500 (± 307)

117 (± 5)

23.6

49.0

300 (± 5)

159 (± 100)

INT

25.1

47.0

691 (± 58)

171 (± 43)

24.4

54.0

281 (± 13)

180 (± 0)

22.2

53.7

332 (± 100)

309 (± 292)

23.7

49.5

244 (± 20)

180 (± 20)

Mean

24.9

50.3

357 (± 34)

83 (± 21)

25.03

49.8

421 (± 58)

160 (66)

24.2

50.7

313 (136)

156 (± 106)

23.3

51.7

209 (± 11)

137 (± 47)