Table 6 Optimization results for first scenario of IEEE 33-bus for various energy systems.
Parameter | Base Case | Case-01 | Case-02 | Case-03 |
|---|---|---|---|---|
APL (KW) | 202.7 | 61.66 | 23.81 | 18.81 |
APL reduction (%) | – | 70 | 88 | 91 |
Cost (million $) | – | 53.52 | 29.36 | 46.29 |
Generator/MMR(MW), Loc | – | 2.6 (6) | 1.336 (30) | 1.248 (30) |
Generator (MVAR) | – | 1.63 | 0.828 | 0.774 |
Solar PV(MW), Loc | – | 0.00 | 0.780 (25) | 0.780 (25) |
Wind (MW), Loc | – | 0.00 | 0.691 (14) | 0.753 (13) |
Wind (MVAR) | – | 0.00 | 0.428 | 0.466 |
VMIN (p.u.) | 0.9131 | 0.967 | 0.981 | 0.9922 |
CO2 emission(ton/year) | – | 16,082 | 8196 | 49.75 |
CO2 Penalty ($) | – | 49,886 | 25,423 | 154.32 |