Table 9 Result of optimization for various energy systems of IEEE 69-bus in terms of APL.

From: Optimal planning of integrated nuclear-hybrid renewable energy systems for electrical distribution networks based on artificial intelligence

Parameter

Base Case

Case-01

Case-02

Case-03

APL (KW)

238.8

24.70

8.13

7.35

APL Reduction (%)

–

90

96

97

Cost (million $)

–

40.81

44.26

52.77

Generator/MMR(MW), Loc

–

2 (61)

1.806 (61)

1.76 (61)

Generator (MVAR)

 

1.239

1.119

1.094

Solar PV(MW), Loc

–

0.00

0.00

0.246(21)

Wind (MW), Loc

–

0.00

0.536 (17)

0.631 (12)

Wind (MVAR)

–

0.00

0.332

0.391

VMIN (p.u)

0.9034

0.973

0.994

0.994

CO2 emission (ton/year)

–

12,264

11,074

70.34

CO2 Penalty ($)

–

38,043

34,351

218.19