Table 5 Detailed parameters of 3, 5 and 7 MVA power transformers.

From: Condition monitoring and fault diagnosis of power transformer based on non-invasive measurement

Model

Transformer 1

Transformer 2

Transformer 3

1

\(P\)

Power rating

3 MVA

5 MVA

7 MVA

2

\(V\)

Voltage rating

33/11 kV

33/11 kV

20/6 kV

3

\(D\)

Number of discs on the HV winding

89

67

69

4

\(OD\)

Outer diameters of the HV winding

582 mm

609 mm

702 mm

5

\(ID\)

Inner diameters of the HV winding

496 mm

503 mm

579 mm

6

\(T\)

Number of the turns in the HV winding

1428

1206

1104

7

\(R\)

Resistance per disc

1.4 Ω

2.4 Ω

0.43 Ω

8

\(L\)

Total inductance per disc

0.16 mH

0.11 mH

0.025 mH

9

\({C}_{g}\)

Ground capacitance per disc

0.08 pF

0.056 pF

0.12 pF

10

\({C}_{s}\)

Series capacitance per disc

2.1 pF

9.0 pF

5.1 pF