Table 6 Limits of voltage distortion according to IEEE standard 519–201441

From: Condition monitoring and fault diagnosis of power transformer based on non-invasive measurement

Bus voltage V at PCC

Individual harmonics (%)

Total harmonic distortion THD (%)

\(V\le 1.0 KV\)

5.0

8.0

\(1.0 KV<V\le 69 KV\)

3.0

5.5

\(69 KV<V\le 161 KV\)

1.5

2.5

\(V>161 KV\)

1.0

1.5