Table 6 Worst-case current THD under heavy non-linear loading, and its reduction via SAPF and hybrid filtering.
Operating mode | Worst case pre filter THD (%) | After SAPF (%) | After hybrid (%) |
|---|---|---|---|
PV only | 45.79 | 8.16 | 4.76 |
PV + BESS charging | 46.66 | 10.48 | 4.79 |
BESS discharge | 16.01 | 2.62 | –(SAPF sufficient) |
Grid only | 24.43 | 11.24 | 2.85 |