Table 4 Results under fault condition: F13|PTP (d = 100 km).

From: Adaptive non unit traveling wave protection algorithm for multi terminal HVDC grids

Rf (Ω)

d4u(1)13 (kV)

ΔE13 (kV)

Fault detection

time (ms)

0

190.23

1.35e-6

0.61

50

76.76

1.21e-7

0.65

100

41.83

1.48e-7

0.69

200

23.38

1.84e-8

0.72

300

22.96

3.69e-8

0.75

500

13.47

7.13e-8

0.76