Table 2 Measured airflow rates for various FS and VOR.
From: Maximizing waste heat recovery from a building-integrated edge data center
Fan Speed (V) | Qa (m3/h) | ||||
|---|---|---|---|---|---|
VOR = 50% | VOR = 60% | VOR = 70% | VOR = 80% | Average | |
20 | 1656.35 | 1631.00 | 1611.08 | 1546.22 | 1611.16 |
25 | 1921.41 | 1923.79 | 1895.86 | 2044.43 | 1946.37 |
30 | 2323.48 | 3211.41 | 2225.76 | 2280.46 | 2510.28 |
35 | 2671.99 | 2767.18 | 2678.88 | 2624.81 | 2685.72 |
40 | 3180.07 | 2952.13 | 2954.41 | 3148.49 | 3058.78 |
45 | 3487.07 | 3412.28 | 3294.93 | 3328.89 | 3380.79 |
50 | 4067.03 | 3835.92 | 3824.37 | 3765.46 | 3873.20 |