Table 19 Dynamic responses of the system.

From: A hybrid fuzzy-PIDD² control strategy for coordinated LFC and AVR in renewable-integrated multi-area power systems

Controller

Optim. Algorithm

∆f1

∆f2

Ptie

Vout1

Vout2

MO∆f1

(Hz)

MU∆f1

(Hz)

MO∆f2

(Hz)

MU∆f2

(Hz)

MOP

(p.u)

MUP

(p.u)

MP− V1

(p.u)

Tr−V1

(Sec.)

Ts−V1

(Sec.)

MP− V2

(p.u)

Tr−V2

(Sec.)

Ts−V2

(Sec.)

PID

PSO

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

PID

GTO

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

PID

MPA

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

PIDD²

PSO

0.006

−0.074

0.024

−0.100

0.002

−0.001

0.463

0.083

3.057

0.285

0.136

2.120

PIDD²

GTO

0.023

−0.103

0.065

−0.148

0.002

−0.001

0.482

0.109

5.722

0.286

0.136

2.122

PIDD²

MPA

0.026

−0.099

0.028

−0.100

0.001

−0.001

0.191

0.138

2.098

0.305

0.144

2.152

FPIDD²+PIDD²

PSO

0.001

−0.018

0.001

−0.020

0.000

0.000

0.451

0.084

5.583

0.292

0.147

2.135

FPIDD²+PIDD²

GTO

0.045

−0.054

0.004

−0.035

0.000

−0.001

0.437

0.110

2.659

0.274

0.146

2.123

FPIDD²+PIDD²

MPA

0.001

−0.010

0.001

−0.015

0.001

0.000

0.341

0.295

4.697

0.313

0.181

2.195