Table 1 International grid code requirements.

From: A new approach for improving dynamic fault ride through capability of gridctied based wind turbines

Country

During fault condition

After fault condition

\(\:{\varvec{V}}_{\varvec{m}\varvec{i}\varvec{n}}\) (pu)

\(\:{\varvec{T}}_{\varvec{m}\varvec{i}\varvec{n}}\) (s)

\(\:{\:\:\:\:\:\:\:\varvec{V}}_{\varvec{m}\varvec{i}\varvec{n}}\) (pu)

\(\:{\varvec{T}}_{\varvec{m}\varvec{i}\varvec{n}}\) (s)

Australia

0.00

0.1

0.7

2

China

0.16

0.625

0.9

3

Canada

0

0.15

0.85

1

Denmark

0.2

0.5

0.9

1.5

Germany

0

0.15

0.9

1.5

India

0.15

0.3

0.85

3

Ireland

0.15

0.625

0.9

3

New Zealand

0

0.2

0.6

1

United States

0.15

0.14

0.8

0.21

United Kingdom

0.15

0.625

0.9

3