Table 1 International grid code requirements.
From: A new approach for improving dynamic fault ride through capability of gridctied based wind turbines
Country | During fault condition | After fault condition | ||
|---|---|---|---|---|
\(\:{\varvec{V}}_{\varvec{m}\varvec{i}\varvec{n}}\) (pu) | \(\:{\varvec{T}}_{\varvec{m}\varvec{i}\varvec{n}}\) (s) | \(\:{\:\:\:\:\:\:\:\varvec{V}}_{\varvec{m}\varvec{i}\varvec{n}}\) (pu) | \(\:{\varvec{T}}_{\varvec{m}\varvec{i}\varvec{n}}\) (s) | |
Australia | 0.00 | 0.1 | 0.7 | 2 |
China | 0.16 | 0.625 | 0.9 | 3 |
Canada | 0 | 0.15 | 0.85 | 1 |
Denmark | 0.2 | 0.5 | 0.9 | 1.5 |
Germany | 0 | 0.15 | 0.9 | 1.5 |
India | 0.15 | 0.3 | 0.85 | 3 |
Ireland | 0.15 | 0.625 | 0.9 | 3 |
New Zealand | 0 | 0.2 | 0.6 | 1 |
United States | 0.15 | 0.14 | 0.8 | 0.21 |
United Kingdom | 0.15 | 0.625 | 0.9 | 3 |