Table 3 The residual values of gas composition prediction and warning values.

From: Intelligent fault diagnosis and operation condition monitoring of transformer based on multi-source data fusion and mining

Constituent

Prewarning value μL/L

Constituent

Prewarning value μL/L

\(\hbox {H}_{2}\)

25.20

\(\hbox {C}_{2}\hbox {H}_{6}\)

15.1

\(\hbox {CH}_{4}\)

11.40

\(\hbox {CO}\)

315

\(\hbox {C}_{2}\hbox {H}_{2}\)

1.55

\(\hbox {CO}_{2}\)

1850

\(\hbox {C}_{2}\hbox {H}_{4}\)

5.60

 Â