Table 6 Regression analysis results for solar heat gain and CEV based on WOA for different glazing types for July and August.
From: Seasonal thermal performance of double and triple glazed windows with effects of window opening area
Location and glazing types | Variable | Regression coefficient (β1) | P-value | R-squared |
|---|---|---|---|---|
1# Double glazing room | Solar heat gain | 634.48 | 0.0004 | 0.995 |
CEV | 876.27 | 0.0003 | 0.997 | |
1# Triple glazing room | Solar heat gain | 518.46 | 0.0005 | 0.993 |
CEV | 712.45 | 0.0003 | 0.996 | |
2# Double glazing room | Solar heat gain | 699.08 | 0.0002 | 0.996 |
CEV | 933.84 | 0.0002 | 0.997 | |
2# Triple glazing room | Solar heat gain | 564.08 | 0.0004 | 0.995 |
CEV | 752.97 | 0.0003 | 0.996 | |
3# Double glazing room | Solar heat gain | 726.85 | 0.0001 | 0.998 |
CEV | 972.47 | 0.0001 | 0.998 | |
3# Triple glazing room | Solar heat gain | 576.92 | 0.0003 | 0.996 |
CEV | 791.88 | 0.0002 | 0.997 |