Table 1 Weight loss parameters of mild steel 1010 in cooling tower system

From: Dual-function of N-substituted tetrabromophthalic inhibitors for eco-friendly control of microbiologically influenced corrosion in industrial cooling systems

System

Average weight loss (mg)

Corrosion rate (mm/year)

Inhibition efficiency (%)

S1

87.4 ± 0.3

1.16

-

S2

106.2 ± 0.5

1.41

-

S3

44.7 ± 0.2

0.59

48.86

S4

13.2 ± 0.5

0.17

85.13

S5

21.4 ± 0.1

0.27

75.97

S6

57.2 ± 0.3

0.75

34.78

S7

25.7 ± 0.5

0.33

71.40

S8

40.4 ± 0.2

0.53

54.23

  1. S1 abiotic control. S2 biotic control. S3 4,5,6,7 -tetrabromo-2-(4-butyl phenyl) isoindoline-1,3-dione (TBID). S4 4,5,6,7 -tetrabromo-2-octylisoindoline-1,3-dione (TOID). S5 4,5,6,7 -tetrabromo-2-(2,5-di-tert-butyl phenyl) isoindoline-1,3-dione (TDID). S6 4,5,6,7 -tetrabromo-2-(4-butyl phenyl) isoindoline-1,3-dione (TBID) with V. injensis. S7 4,5,6,7 -tetrabromo-2-octylisoindoline-1,3-dione (TOID) with V. injensis. S8 tetrabromo-2-(2,5-di-tert-butyl phenyl) isoindoline-1,3-dione (TDID) with V. injensis.