Table 2 Voltage distortion limits in IEEE STD 519–201467.

From: Enhancing stability and power quality in electric vehicle charging stations powered by hybrid energy sources through harmonic mitigation and load management

Voltage distortion limits (IEEE STD 519–2014)

Bus Voltage VVV at PCC

Individual harmonic (%)

Total harmonic distortion (THD) (%)

\(\:\text{V}\le\:1.0\:\text{k}\text{V}\)

5.0

8.0

\(\:1\:\text{k}\text{V}\:<\text{V}\:\le\:69\:\text{k}\text{V}\)

3.0

5.0

\(\:69\:\text{k}\text{V}\:<\text{V}\:\le\:161\:\text{k}\text{V}\)

1.5

2.5

161 kV\(\:<\)V

1.0

1.5