Table 8 Performance comparison of different protection schemes.

From: Active line model identification protection based on characteristic frequency phase for dual-end weakly-fed AC system

Protection scheme

Two terminal weak feed AC system?

Affected by the accuracy of line parameters?

Fully consider the impact of control strategies?

The setting value depends on the simulation setting?

Anti-noise/fault resistance

9,10,11,12

No

Yes

No

Yes

No /120Ω

10,13,14

Yes

No

No

Yes

No/100Ω

20,21,22

No

Yes

No

No

No /100Ω

Proposed protection

Yes

No

Yes

No

25 dB/300Ω