Table 14 Comparison of the PAs average accuracy (validation data accuracy) and the PAs’ detection time in different scenarios.

From: A fault classification scheme based on protective agents for microgrid with parameters impact analysis

Parameter

Fault detection accuracy (%)

FT and FP accuracy (%)

Fault location error (%)

The PAs’ Fault Detection Time

Scenarios

DNN-1

DNN-2

DNN-1

DNN-2

DNN-1

DNN-2

DNN-1

DNN-2

Scenario 1

98.73

99.90

98.41

99.63

3.16

1.98

14 msec

18 msec

Scenario 2

97.94

98.94

97.8

98.87

3.09

1.85

13 msec

16 msec

Scenario 3

97.11

98.26

97.13

98.27

4.35

2.92

16 msec

18 msec

Scenario 4

97.83

99.03

97.82

99.03

3.57

2.08

13 msec

14 msec

Scenario 5

96.96

98.37

97.08

98.28

4.69

3.2

14 msec

17 msec

Scenario 6

96.54

97.7

96.63

97.79

4.99

3.33

19 msec

22 msec

Scenario 7

96.67

98.03

96.73

98.04

4.76

3.14

18 msec

22 msec

Scenario 8

98.66

99.895

98.55

99.79

2.34

1.575

22 msec

24 msec