Table 2 The parameters of the studied microgrid.

From: A fault classification scheme based on protective agents for microgrid with parameters impact analysis

Element

Name

Value

Transformers

T-7

13.8 kV/0.48 kV, X/R = 6, and Z = 5%

T-1, T-3, T-6, and T-16

0.48 kV/0.48 kV, X/R = 5, and Z = 1%

Lines, and Laterals

Line 12, Line 34, Line 56, Line 78, and Lateral 23

Size (AWG2), 68.58 m, Lateral 50% of the main line

Line 23, Lateral 12, Lateral 34, and Lateral 56

Size (AWG00), 22.86 m, Lateral 50% of the main line

Loads

L-2 and L-4

90 kW and 45 kVAR

L-5

90 kW and − 40 kVAR

L-8

90 kW and − 20 kVAR

L-12, L-34, L-56

50 kW and 20 kVAR

L-23

50 kW and 10 kVAR

DGs

DG-BESS and DG-PV

100 kW, unity power factor (3-phase capacitor bank (15 kVA))

DG-SG

100 kW, PF = 0.8

Studied Network

Voltage

0.48 kV

Frequency

50 Hz