Table 21 Pre-fault and fault current maximum values at the PA locations for fault on different lines of scenario 1 in the islanded operation mode of the studied microgrid.
Faulty line in the islanded operation mode of the microgrid | Pre-fault currents at the PA locations (A) | |||||||
|---|---|---|---|---|---|---|---|---|
PA-12 | PA-21 | PA-23 | PA-32 | PA-34 | PA-43 | PA-56 | PA-65 | |
173Â A | 173Â A | 175Â A | 175Â A | 133Â A | 133Â A | 237Â A | 237Â A | |
Fault currents (in A and p.u) at the PA locations | ||||||||
Fault on Line 12 | 188Â A | 132Â A | 220Â A | 220Â A | 175Â A | 175Â A | 217Â A | 217Â A |
1.08 In | 0.76 In | 1.25 In | 1.25 In | 1.31 In | 1.31 In | 0.91 In | 0.91 In | |
Fault on Line 23 | 171Â A | 171Â A | 181Â A | 255Â A | 149Â A | 149Â A | 239Â A | 239Â A |
0.97 In | 0.97 In | 1.03 In | 1.45 In | 1.12 In | 1.12 In | 1.00 In | 1.00 In | |
Fault on Line 34 | 158Â A | 158Â A | 186Â A | 186Â A | 255Â A | 125Â A | 262Â A | 262Â A |
0.90 In | 0.90 In | 1.06 In | 1.06 In | 1.91 In | 0.94 In | 1.10 In | 1.10 In | |
Fault on Line 56 | 142Â A | 142Â A | 208Â A | 208Â A | 213Â A | 213Â A | 175Â A | 301Â A |
0.81 In | 0.81 In | 1.19 In | 1.19 In | 1.60 In | 1.60 In | 0.74 In | 1.27 In | |